ANZ Consulting Engineering is a registered Special Inspection Agency qualified to perform inspections in New York City.

SPRAYED FIRE-RESISTANT MATERIALS

Building Code: 1704.11

All sprayed fire-resistant materials applied to floor, roof and wall assemblies and structural members as designated in the approved construction documents must be inspected. ANZ can perform visual inspection after the rough installation of all electrical, sprinkler, mechanical and plumbing systems and suspension systems for ceilings.

EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

Building Codes: 1704.13 / 2702

All Exterior Insulation and Finish Systems (EIFS) installed more than 15 feet above adjacent finished grades must be inspected. ANZ can perform visual inspection of these EIFS systems to verify compliance with the approved construction documents including proper attachment to the building’s structural, installation of waterproofing membranes, weeps, and drains. We will also check that all mold prevention features are in conformance with the manufacturer’s installation guidelines.

SMOKE CONTROL SYSTEMS

Building Code: 1704.15

All active smoke control systems including stair including smoke exhaust systems, stair pressurization systems, and elevator pressurization systems, must be inspected and tested. ANZ can perform the required visual inspection of the smoke control systems and perform the function performance testing and air balancing procedures by our of our certified air balancers.

MECHANICAL SYSTEMS

Building Code: 1704.16

All mechanical systems requiring a Certificate of Compliance by the Administrative Code Section 28-116.4.1  must be inspected for conformance with the construction documents. ANZ can perform visual inspection of all installed mechanical systems, and required testing per applicable NYC Building Codes.

FUEL-OIL STORAGE AND FUEL-OIL PIPING SYSTEMS

Building Code: 1704.17

All fuel-oil storage equipment including tanks, pumps, valves, piping, hangers and bracing, and terminals must be inspected in accordance with the contract documents. ANZ can perform visual inspection of the installed systems and verify proper testing of all fuel oil storage tanks in accordance with Section 1308 of the NYC Mechanical Code.

SOIL PERCOLATION TEST - PRIVATE ON-SITE STORM WATER DRAINAGE DISPOSAL SYSTEMS, AND DETENTION FACILITIES

Building Code: 1704.21.1.2

All soil percolation tests performed by the contractor must be performed under the supervision of a Special Inspector. ANZ can assist in overseeing the percolation tests and verify they have been performed in accordance with the provisions of Section 1114.2.2 of the NYC Plumbing Code.

PRIVATE ON-SITE STORM WATER DRAINAGE DISPOSAL SYSTEMS, AND DETENTION FACILITIES INSTALLATION

Building Code: 1704.21.2

All storm water detention and retention systems including roof detention systems must be inspected. ANZ can perform visual inspection of the installed detention facilities to ensure proper materials are used, proper placement of fill materials, adequate volume is maintained, are proper flow control devices are used. As part of the inspection we would witness a water tightness test on all detention tanks as facilitated by the Contractor.

INDIVIDUAL ON-SITE PRIVATE SEWAGE DISPOSAL SYSTEMS INSTALLATIONS

Building Code: 1704.22

All on site sewage disposal systems must be inspected. ANZ can perform visual inspection of the installed systems for conformance with the rules of the department.

SOIL PERCOLATION TEST - INDIVIDUAL ON-SITE PRIVATE SEWAGE DISPOSAL SYSTEMS

Building Code: 1704.22

All soil percolation tests performed by the contractor must be performed under the supervision of a Special Inspector. ANZ can assist in overseeing the percolation tests and verify they have been performed in accordance with the provisions of Section 1114.2.2 of the NYC Plumbing Code.

SPRINKLER SYSTEMS

Building Code: 1704.23

All new and altered sprinkler systems must be inspected. ANZ can perform visual inspection of the sprinkler systems including witness of the required hydrostatic pressure test as performed by the Licensed Fire Supression Contactor.

STANDPIPE SYSTEMS

Building Code: 1704.24

All new and altered standpipe systems must be inspected. ANZ can  perform visual inspection of the standpipe systems including witness of the required hydrostatic pressure test as performed by the Licensed Fire Supression Contactor.

CHIMNEYS

Building Code: 1704.26

All new and altered boilers, chimney connectors, and heating systems must be inspected. ANZ can perform visual inspection of all required heating systems to verify compliance with the construction documents.

FIRE-RESISTANT PENETRATIONS AND JOINTS (FIRESTOP)

Building Code: 1704.27

All penetration firestop systems and fire-resistant joint systems must be inspected. ANZ can perform visual inspection of all penetrations and joints to verify compliance with standards ASTM E 2174 and ASTM E 2393.

Structural Steel - Welding

All new structural steel welds shall be inspected to confirm compliance with the construction documents. ANZ can perform visual inspection of welds in accordance with AWS D1.1.

Structural Steel - Details

The steel frame shall be inspected to verify compliance with the detail shown on the approved construction documents including bracing, stiffening, member location and proper application of joint details at each connection. ANZ can perform visual inspection of the details.

Structural Steel - High Strength Bolting

Installation of high-strength bolts are to be inspected in accordance with the construction documents. ANZ can perform visual inspection of the bolting periodically in accordance with AISC 360.

Structural Stability - Existing Buildings

Existing structures shall be inspected prior to demolition activities to verify the ability of the structural system to remain in position without incurring damage from construction activities and loading. ANZ can perform inspection of the temporary protection measures put in place in accordance with the building code and the construction documents.

FLOOD HAZARD MITIGATION

Building Code: 1704.29, G105

All buildings located in areas of special flood hazard must be inspected. ANZ can perform inspection of buildings to verify compliance with Appendix G of the NYC Building Code. The inspection protocol will include verification of lowest floor elevation, and verification that the building has been constructed using methods and practices that minimize flood damage in accordance with the approved construction documents.

LUMINOUS EGRESS PATH MARKINGS

Building Code: 1704.30

All photoluminescent egress path markings must be inspected. ANZ can perform the visual inspection of all required markings to verify compliance with the approved construction documents, manufacturer’s installation requirements, and department rules & regulations.

EMERGENCY & STANDBY POWER SYSTEMS (GENERATORS)

Building Code: 1704.31

All photoluminescent egress path markings must be inspected. ANZ can perform the visual inspection of all required markings to verify compliance with the approved construction documents, manufacturer’s installation requirements, and department rules & regulations.

POST-INSTALLED ANCHORS

Building Code: 1704.32

All post installed anchors including mechanical anchors, adhesive anchors, and screw anchors must be inspected. ANZ can perform visual inspection of the anchor systems to ensure the installation is being performed in accordance with the Manufacturer’s Printed Installation Instructions (MPII). We can also perform proof-load testing using one of our hydraulicaly actuated pull-testing devices.

SEISMIC ISOLATION SYSTEMS

Building Code: 1707.8

Building Structures designated in Seismic Design Category C or D must be inspected for proper seismic isolation system installation. ANZ can perform visual inspection of all required mechanical, plumbing, fuel gas, and electrical components to confirm compliance with the approved construction documents.

PROTECTION OF EXPOSED FOUNDATION INSULATION

IA1

Insulation will be visually inspected to verify proper protection where appied to the exteior of cellar walls, crawl space walls and at the perimeter of slab on grade floors.

INSULATION PLACEMENT & R-VALUES

IIA2

Insulation will be visually inspected to verify proper protection where appied to the exteior of cellar walls, crawl space walls and at the perimeter of slab on grade floors.

FENESTRATION AND DOOR U FACTOR AND PRODUCT RATINGS

IIA3
Fenestration will be visually inspected to verify conformance of all required U-factors, SHGC and VT values with the construction documents by verifying the manufacturer’s NFRC labels. When not labeled, ratings in ECC Tables C303.1.3(1), (2) and (3) will be used.

FENESTRATION AIR LEAKAGE

IIA4
Windows and sliding or swinging door assemblies, except site-built windows and/or doors, shall be visually inspected to verify that installed assemblies are listed and labeled by the manufacturer to the referenced standard. For curtain wall, storefront glazing, commercial entrance doors and revolving doors, the testing reports shall be reviewed to verify that the installed assembly complies with the standard cited in the approved plans. Weather seals at loading docks will be visually verified.

FENESTRATION AREAS

IIA5
Dimensions of windows, doors and skylights shall be verified by visual inspection.

AIR BARRIER TESTING

IIA7
ANZ will utilize our calibrated blower door testing apparatus to perform the required testing. Air Barrier Testing will be performed in accordance with section ECC C402.5.1.3.1 of the NYC Energy Code. Blower door testing will be performed in accordance with standard ASTM E779.

AIR BARRIER CONTINUITY PLAN TESTING

IIA8

Insulation will be visually inspected to verify proper protection where appied to the exteior of cellar walls, crawl space walls and at the perimeter of slab on grade floors.

VESTIBULES

IIA9
Air Barrier Continuity Plan Testing will be performed in accordance with section ECC C402.5.1.3.1 of the NYC Energy Code.

MECHANICAL AND SERVICE WATER HEATING INSPECTIONS

FIREPLACES

IIB1
Each fireplace will be visually inspected for conformance with the contract documents including required provisions for combustion air and tight fiting doors. Additionally, our field inspector will perform a smoke test on all required chimney liners if TR-1 Chimney inspections are required.

SHUTOFF DAMPERS

IB1, IIB1
All dampers integral to the building envelope will be visually inspected to verify compliance with the construction documents.

HVAC-R, COMMERCIAL KITCHEN EQUIPMENT, AND SERVICE WATER HEATING EQUIPMENT

IB3
HVAC, commercial kitchen equipment, and service water heating equipment will be visually inspected to verify compliance with the construction documents.

HVAC-R AND SERVICE WATER HEATING SYSTEM CONTROLS

IB4

HVAC, commercial kitchen equipment, and service water heating system controls will be inspected and proper operation demonstrated with the assistance of the contractor.

HVAC-R AND SERVICE WATER PIPING DESIGN & INSULATION

IB5

All piping will be visually inspected to verify the insulation is in accordance with the contract documents.

DUCT LEAKAGE TESTING, INSULATION AND DESIGN - IB6

IB6

All duct systems will be visually inspected to verify the insulation is in accordance with the contract documents. Additionally, any systems operating in excess of 3″ in. water gauge will be tested for tightness.

ELECTRICAL POWER AND LIGHTING SYSTEMS

METERING – IIC1
Visual inspection will be performed to confirm the presence of all required meters for monitoring total electrical energy usage and/or total fuel use.

LIGHTING IN DWELLING UNITS – IIC2
All lamps will be visually inspected to verify compliance with the code’s high efficacy requirements.

INTERIOR LIGHTING POWER – IIC3
All installed interior lighting shall be visually inspected to verify compliance with the lighting power allowances as indicated on the contract documents.

EXTERIOR LIGHTING POWER – IIC4
All installed exterior lighting shall be visually inspected to verify compliance with the lighting power allowances as indicated on the contract documents.

LIGHTING CONTROLS – IIC5
Installed lighting controls systems will be both visually inspected and tested for proper functionality in accordance with the contract documents. This will include:
▪ occupant sensors
▪ manual interior lighting controls
▪ light-reduction controls
▪ automatic lighting shutoff
▪ daylight zone controls
▪ sleeping unit controls
▪ exterior lighting controls
▪ egress illumination controls

PROOF-LOADING

Using our calibrated pull testing equipment, ANZ can perform pull testing for concrete installed anchoring systems. Proof-load verification is often required by Engineers as part of approval of post-installed anchoring systems under the TR-1 Post Installed Anchors special inspection requirements. This includes verification for epoxy anchors, mechanical anchors, and screw anchors.

SPRINKLER HYDROSTATIC PRESSURE TESTING

ANZ facilitates sprinkler hydrostatic pressure testing on systems requiring TR-1 Sprinkler System sign off. We can provide a fully calibrated pressure gauge for use by the contactor in conducting the testing.

SMOKE TESTING

New and altered chimneys are required by the Department to be smoke tested to verify integrity of the chimney liner. ANZ can perform smoke testing as required by the code for verification of chimney tightness.

BLOWER DOOR TESTING

The New York City Energy Conservation Code required blower door testing for residential dwelling units, and for new commercial building greater than 25,000 sq. ft. ANZ can perform the required testing using our calibrated blower door testing apparatus.
ANZ Inspections and Testing Laboratory provides a full line of monitoring services for ground-up construction and major alteration projects. Our certified inspectors can provide services for vibration monitoring, crack gauge monitoring and optical monitoring.

VIBRATION MONITORING

The New York City Building Code requires monitoring of adjacent building structures within certain distances when excavation work is performed per section 330.9.4.4., and during underpinning procedures in accordance with Section 1814.

Monitoring services are performed in accordance with a monitoring plan developed by the project’s registered design professional indicating the scope, frequency of monitoring, acceptable tolerances, and reporting criteria for when tolerances are exceeded.

ANZ Inspections and Testing Laboratory performs all monitoring services using reliable vibration monitor assemblies complete with multiple types of triaxial geophones. Each assembly is deployed to the job site in a weather-protected case with an internal wireless router for transmission of all data to a remote central station. When permanent power is not available on site, we can provide battery stations or solar panels for on-site power generation.

CRACK MONITORING

As part of all required monitoring services, crack strain gauges are monitored by our certified inspectors for building movement during heavy construction activities.

OPTICAL MONITORING

ANZ Inspections and Testing Laboratory works with our partner Licensed Land Surveyor to provide required optical monitoring services.